Cable Management Network Servers

This topic describes nodes in the air-cooled cabinet with diagrams and pictures showing where to find the ports on the nodes and how to cable the nodes to the management network switches.

HPE Hardware

HPE DL385

Diagram of Rear View of HPE ProLiant DL385 Gen10 Plus

  • The OCP Slot is noted (number 7) in the image above.
    • This is the bottom middle slot to the left of the VGA port.
    • Ports are numbered left-to-right: the far left port is port 1.
  • The PCIe Slot 1 is on the top left side of the image above (under number 1).
    • Ports are numbered left-to-right: the far left port is port 1.

HPE DL325

Diagram of Rear View of HPE ProLiant DL325 with OCP

  • The OCP Slot is noted (number 9) in the image above.
    • This is the slot on the bottom left of the node.
    • Ports are numbered left-to-right: the far left port is port 1.
  • The PCIE Slot 1 is on the top left side of the image above (under number 1).
    • Ports are numbered left-to-right: the far left port is port 1.

HPE Worker Node Cabling

Server Port Management Network Port Speed Use / Configuration
OCP port 1 spine or aggregation pair, switch 1/2 25Gb Management Network NMN/HMN/CAN
OCP port 2 spine or aggregation pair, switch 2/2 25Gb Management Network NMN/HMN/CAN

SHCD Example

hostname Source Destination Destination
wn01 x3000u04ocp-j1 x3000u12-j7 sw-25g01
wn01 x3000u04ocp-j2 x3000u13-j7 sw-25g02

Diagram of HPE Worker Node Cabling

HPE Master Node Cabling

Dual Card Installations

The table below describes the cabling of dual card configurations. Also read notes in this section to see other possible customer-based configurations.

Server Port Management Network Port Speed Use / Configuration
OCP port 1 spine or aggregation pair, switch 1/2 25Gb Management Network NMN/HMN/CAN
OCP port 2 NONE NONE NONE
PCIe Slot 1 port 1 spine or aggr pair, switch 2/2 25Gb Management Network NMN/HMN/CAN
PCIe Slot 1 port 2 NONE (See note below for ncn-m001) NONE Site (See note below for ncn-m001)

SHCD Example

hostname Source Destination Destination
mn01 x3000u01ocp-j1 x3000u12-j1 sw-25g01
mn01 x3000u01s1-j1 x3000u13-j1 sw-25g02

Diagram of HPE Master Node Cabling

NOTE: Master 1 (ncn-m001) is required to have a site connection for installation and non-CAN system access. This can have several configurations depending on customer requirements/equipment:

  • Dual 10/25Gb card configurations as described in the table above should use PCIe Slot 1, Port 2 as a site connection if the customer supports 10/25Gb.
  • If the customer does not support 10/25Gb speeds (or connection type) and requires RJ45 copper or 1Gb, then a new and separate card will be installed on ncn-m001 and that card will provide site connectivity.
  • Another possibility (non-HPE hardware mainly) is that a built-in 1Gb port will be used if available (similar to Shasta v1.3 PoR on Gigabyte hardware).

HPE Storage Node Cabling

Server Port Management Network Port Speed Use / Configuration
OCP port 1 spine or aggregation pair, switch 1/2 25Gb Management Network NMN/HMN/CAN
OCP port 2 spine or aggregation pair, switch 1/2 25Gb Storage SUN (future use)
PCIe Slot 1 port 1 spine or aggregation pair, switch 2/2 25Gb Management Network NMN/HMN/CAN
PCIe Slot 1 port 2 spine or aggregation pair, switch 2/2 25Gb Storage SUN (future use)

SHCD Example

hostname Source Destination Destination
sn01 x3000u17s1-j2 x3000u34-j14 sw-25g02
sn01 x3000u17s1-j1 x3000u34-j8 sw-25g02
sn01 x3000u17ocp-j2 x3000u33-j14 sw-25g01
sn01 x3000u17ocp-j1 x3000u33-j8 sw-25g01
The OCP ports go to the First switch and the PCIe ports go to the Second switch. OCP port 1 and PCIe port 1 form a Bond. OCP port 2 and PCIe port 2 form a Bond.
Diagram of HPE Storage Node Cabling for Small System

For systems that include 4 aggregation switches the cabling will look like the following.

Diagram of HPE Storage Node Cabling for Large System

SHCD Example with four aggregation switches.

hostname Source Destination Destination
sn01 x3000u10ocp-j2 x3000u36-j5 sw-25g04
sn01 x3000u10s1-j2 x3000u35-j5 sw-25g03
sn01 x3000u10ocp-j1 x3000u34-j6 sw-25g02
sn01 x3000u10s1-j1 x3000u33-j6 sw-25g01

HPE UAN Cabling

Server Port Management Network Port Speed Use / Configuration
OCP port 1 spine or aggregation pair, switch 1/2 25Gb Management Network NMN
OCP port 2 spine or aggregation pair, switch 1/2 25Gb Management Network CAN bond
PCIe Slot 1 port 1 spine or aggregation pair, switch 2/2 25Gb NONE (Shasta v1.4)
PCIe Slot 1 port 2 spine or aggregation pair, switch 2/2 25Gb Management Network CAN bond

SHCD Example

hostname Source Destination Destination
uan01 x3000u17s1-j2 x3000u34-j14 sw-25g02
uan01 x3000u17s1-j1 x3000u34-j8 sw-25g02
uan01 x3000u17ocp-j2 x3000u33-j14 sw-25g01
uan01 x3000u17ocp-j1 x3000u33-j8 sw-25g01

Diagram of HPE UAN Cabling

HPE Apollo 6500 XL645D

Diagram of Rear View of HPE Apollo 6500 XL645D

  • The XL645D has two servers in the same chassis.
  • The iLO BMC RJ45 port is a shared network port. Both iLO/BMC traffic and compute node traffic could transit this link.
    • Isolating this port to iLO/BMC only traffic is not possible within firmware configuration alone.
    • iLO configuration settings must be paired with management switch port settings to ensure only BMC traffic exits the port.
    • The iLO firmware must be set to tag traffic to VLAN 4. The switch port must be set to trunk VLAN 4.
  • Ports on the OCP card are numbered left-to-right: the far left port is port 1.

Apollo XL645D Cabling (per server)

Server Port Management Network Port Speed Use / Configuration
OCP port 1 1G leaf switch 1Gb Management Network NMN
OCP port 2 None None None
OCP port 3 None None None
OCP port 4 None None None
iLO 1G leaf switch 1Gb Management Network HMN

HPE Apollo 6500 XL675D

Diagram of Rear View of HPE Apollo 6500 XL675D

  • Two PCIe slots (chassis slots 21 and 22) are highlighted. One will contain the 1Gb management network card and one will be for the HSN.
  • The iLO BMC RJ45 port is a shared network port. Both iLO/BMC traffic and compute node traffic could transit this link.
    • Isolating this port to iLO/BMC only traffic is not possible within firmware configuration alone.
    • iLO configuration settings must be paired with management switch port settings to ensure only BMC traffic exits the port.
    • The iLO firmware must be set to tag traffic to VLAN 4. The switch port must be set to trunk VLAN 4.
  • Ports on the PCIe card are numbered left-to-right: the far left port is port 1.

Apollo XL675D Cabling

Server Port Management Network Port Speed Use / Configuration
PCIe port 1 1G leaf switch 1Gb Management Network NMN
PCIe port 2 None None None
PCIe port 3 None None None
PCIe port 4 None None None
iLO 1G leaf switch 1Gb Management Network HMN

Gigabyte/Intel Hardware

Worker Node Cabling

Diagram of Gigabyte Worker Node

Server Port Management Network Port Speed Use / Configuration
PCIe Slot 1 port 1 spine or aggregation pair, switch 1/2 40Gb Management Network NMN/HMN/CAN
PCIe Slot 1 port 2 spine or aggregation pair, switch 2/2 40Gb Management Network NMN/HMN/CAN

SHCD Example

hostname Source Destination Destination
wn01 x3000u07s1-j1 x3000u24L-j4 sw-smn02
wn01 x3000u07s1-j2 x3000u24R-j4 sw-smn03

Diagram of Gigabyte Worker Node Cabling

NOTE: Cabling of ncn-w001 has changed in Shasta v1.4. Please see ncn-m001 note below.

Master Node Cabling

Diagram of Gigabyte Master Node

Server Port Management Network Port Speed Use / Configuration
PCIe Slot 1 port 1 spine or aggregation pair, switch 1/2 40Gb Management Network NMN/HMN/CAN
PCIe Slot 1 port 2 spine or aggregation pair, switch 2/2 40Gb Management Network NMN/HMN/CAN
LAN0 port 1 NONE (See note below for ncn-m001) NONE Site (See note below for ncn-m001)

SHCD Example

hostname Source Destination Destination
mn01 x3000u01s1-j1 x3000u24L-j1 sw-smn02
mn01 x3000u01s1-j2 x3000u24R-j1 sw-smn03

Diagram of Gigabyte Master Node Cabling

NOTE: Master 1 (ncn-m001) is required to have a site connection for installation and non-CAN system access. In Shasta versions <=1.3 this connection was on ncn-w001. This can have several configurations depending on customer requirements/equipment:

  • The default configuration for Gigabyte systems uses the built-in 1Gb lan0 port for site connection on ncn-m001.
  • If the customer requires connectivity greater than 1Gb (or a different connection type), then a new and separate card will be installed on ncn-m001 and that card will provide site connectivity.

Storage Node Cabling

Diagram of Gigabyte Storage Node

Server Port Management Network Port Speed Use / Configuration
PCIe Slot 1 port 1 spine or aggregation pair, switch 1/2 40Gb Management Network NMN/HMN/CAN
PCIe Slot 1 port 2 spine or aggregation pair, switch 2/2 40Gb Management Network NMN/HMN/CAN

SHCD Example

hostname Source Destination Destination
sn01 x3000u13s1-j1 x3000u24L-j7 sw-smn02
sn01 x3000u13s1-j2 x3000u24R-j7 sw-smn03

Diagram of Gigabyte Storage Node Cabling

UAN Cabling

Server Port Management Network Port Speed Use / Configuration
LAN0 port 1 leaf (see note) 1Gb Management Network NMN
PCIe Slot 1 port 1 spine or aggregation pair, switch 1/2 40Gb Management Network CAN bond
PCIe Slot 1 port 2 spine or aggregation pair, switch 2/2 40Gb Management Network CAN bond

SHCD Example

hostname Source Destination Destination
uan01 x3000u27s1-j1 x3000u24L-j10 sw-smn02
uan01 x3000u27s1-j2 x3000u24R-j10 sw-smn03

Diagram of Gigabyte UAN Cabling

NOTE that there are a couple configurations possible for LAN0:

  • Existing Gigabyte systems on Dell and Mellanox network hardware will use the (existing) Dell leaf port.
  • Any Gigabyte system on Aruba network hardware will use an Aruba 6300 (for the 1Gb port).
  • Optionally a 10/25Gb card could be added in an Aruba hardware system to match the HPE UANs.