Power off HPE Cray EX liquid-cooled and standard racks.
HPE Cray EX liquid-cooled cabinet CDU and PDU circuit breakers are controlled manually.
When the PDU breakers are switched to OFF
, the Chassis Management Modules (CMMs) and Cabinet Environmental Controllers (CECs) are also powered off.
Warning: The cabinet 480VAC power bus bars remain energized. Facility power must be disconnected to completely remove power from the cabinet. Follow lockout-tagout
procedures for the site before maintenance.
HPE Cray standard EIA racks typically include two redundant PDUs. Some PDU models may require a flat-blade screwdriver to open or close the PDU circuit breakers.
Warning: The cabinet PDUs remain energized when circuit breakers are OFF
. Facility power must be disconnected or the PDUs must be unplugged to completely remove power from the rack. Follow
lockout-tagout
procedures for the site before maintenance.
sat
command. See the “SAT Authentication” section of the HPE Cray EX System Admin Toolkit (SAT) product stream
documentation (S-8031
) for instructions on how to acquire a SAT authentication token.If the system does not include HPE Cray EX liquid-cooled cabinets, then skip the next section and proceed to Power off standard rack PDU circuit breakers.
Check CDU control panel for alerts or warnings and resolve any issues before continuing.
(ncn-m#
) Check the power status before shutdown.
This example shows cabinets 1000-1003.
cray power status list --xnames "x[1000-1003]c[0-7]" --format json
(ncn-m#
) Shut down services and power off liquid-cooled cabinets.
sat bootsys shutdown --stage cabinet-power
This command suspends the hms-discovery
cron job and recursively powers off the liquid-cooled cabinet chassis.
The sat bootsys shutdown
command may fail to power off some cabinets and indicate that requests to PCS have timed out. In this case, the sat
command may be run with an increased --api-timeout
option:
sat --api-timeout 180 bootsys shutdown --stage cabinet-power
(ncn-m#
) Verify that the hms-discovery
cron job has been suspended.
If that is the case, then the SUSPEND
column should be True
in the output of the following command:
kubectl get cronjobs -n services hms-discovery
Example output:
NAME SCHEDULE SUSPEND ACTIVE LAST SCHEDULE AGE^M
hms-discovery */3 * * * * True 0 117s 15d
(ncn-m#
) Check the power off status.
This example shows cabinets 1000-1003.
cray power status list --xnames "x[1000-1003]c[0-7]" --format json
Rectifiers (PSUs) should indicate that DC power is OFF
(AC OK
means the power is on).
Set the cabinet PDU circuit breakers to OFF
for each shelf.
The AC OK
LED on each PSU will remain amber for about 30 seconds (AC lost
) until the system de-energizes, then it will extinguish.
NOTE
If the TDS cabinet rack-mounted coolant distribution unit (MCDU) is receiving power from the PDUs in the management cabinet, then the MCDU may stay on after the TDS cabinet PDU
circuit breakers are set to OFF
. This is expected.
CAUTION: Do not power off the CDU if it is actively cooling other equipment.
If other systems are not being cooled by the floor-standing CDU, then open the CDU rear door to access the control panel and set the circuit breakers to OFF
.
(ncn-m#
) Check the power status before shutdown.
This example shows nodes in cabinets 3001 - 3003.
cray power status list --xnames "x300[1-3]c0s[1,3,5,7,9,11,13,15,17,19,21,23,25,27,29,31,33,35]b[1-4]n0" --format json
In this example, the system includes only 2U servers and there are no state manager entries for even-numbered U-positions (slots); those would return an error.
Example output:
{
"status": [
{
"xname": "x3001c0s1b1n0",
"powerState": "on",
"managementState": "available",
"error": "",
"supportedPowerTransitions": [
"On",
"Soft-Off",
"Off",
"Soft-Restart",
"Force-Off",
"Init",
"Hard-Restart"
],
"lastUpdated": "2023-02-08T23:19:31.182851004Z"
},
{
"xname": "x3003c0s19b1n0",
"powerState": "off",
"managementState": "available",
"error": "",
"supportedPowerTransitions": [
"On",
"Soft-Off",
"Off",
"Soft-Restart",
"Force-Off",
"Init",
"Hard-Restart"
],
"lastUpdated": "2023-02-08T23:19:31.18712898Z"
},
...
]
}
(ncn-m#
) Use PCS to power off HPE Cray standard racks for non-management nodes.
CAUTION: Do not power off the management cabinet. Verify that the components names (xnames) specified in the following command line do not accidentally power off management cabinets.
This example shuts down racks 3001 - 3003.
cray power transition off --xnames "x300[1-3]c0s[1,3,5,7,9,11,13,15,17,19,21,23,25,27,29,31,33,35]b[1-4]n0" --format json
(ncn-m#
) Check the status of the PCS power off command and affected components.
cray power transition describe 6e495247-73b6-44d0-8059-df47b650f1f8 --format json
cray power status list --xnames "x300[1-3]c0s[1,3,5,7,9,11,13,15,17,19,21,23,25,27,29,31,33,35]b[1-4]n0" --format json
Set each cabinet PDU circuit breaker to OFF
.
A slotted screwdriver may be required to open PDU circuit breakers.
To power off Motivair liquid-cooled chilled doors and CDUs, locate the power off switch on the CDU control panel and set it to OFF
.
Refer to vendor documentation for the chilled-door cooling system for power control procedures when chilled doors are installed on standard racks.
Return to System Power Off Procedures and continue with next step.